ET200K 3 phase transformer based industrial online ups 200kva

ET200K 3 phase transformer based industrial online ups 200kva

3 Phase UPS | 200KVA/200KW | 380V/400V/415V | Battery Voltage: 360Vdc

Prostar ET200K is three-phase industrial online UPS 200kVA designed to protect critical equipment against power interruptions and voltage disturbances. It features double-conversion technology, a 1.0 output power factor, less than 3% input current THDi at full load, zero transfer time, and support for up to eight parallel units. VRLA batteries are standard; lithium-ion compatibility is optional.

The system uses online double-conversion technology to regulate output power independently of normal input voltage fluctuations. It delivers a pure sine wave output, supports three-phase, four-wire-plus-protective-earth connections, and provides a nominal output voltage of 380V, 400V, or 415V AC.

For applications requiring higher system capacity or parallel redundancy, the ET200K online UPS 200kVA supports parallel operation of up to 8 units.

Table of Contents

Why Choose the ET200K Industrial Online UPS 200kVA?

Selecting an industrial UPS requires more than matching the nominal kVA rating. Engineers must evaluate active power capacity, voltage stability, harmonic distortion, overload performance, battery autonomy, and maintenance requirements.

The ET200K combines a 200kVA rating with 200kW of active power. This makes the online ups 200kva suitable for facilities with high power demand and equipment sensitive to voltage disturbances.

ET200K Online UPS 200kVA Power Protection for Industrial Applications

 

200kVA/200kW Capacity with Unity Power Factor

Many industrial loads require substantial active power to operate motors, automation systems, control equipment, and production machinery. A UPS with a lower output power factor may reach its kW limit before reaching its kVA limit.

The ET200K has a rated output power factor of 1.0.

ParameterET200K specificationEngineering benefit
Rated apparent power200kVADefines the UPS capacity in kVA
Rated active power200kWSupports up to 200kW of rated active load
Output power factor1.0Makes rated kVA equal to rated kW
Output voltage380/400/415VacSupports common three-phase industrial distribution voltages
Output waveformPure sine waveSuitable for sensitive electronic loads

It means the ET200K can deliver up to 200kW of active power at its rated conditions. Actual system sizing must also account for load current, power factor, harmonic content, transient demand, and the manufacturer’s operating limits.

For example, a facility with a 160kW steady-state load would use 80% of the UPS’s rated active power. This leaves 40kW of nominal active-power headroom, although transient loads and future expansion must be assessed separately.

Online Double-Conversion Technology with Zero Transfer Time

The ET200K uses online double-conversion technology. Incoming AC power is converted to DC and then reconstructed as regulated AC power through the inverter.

This process reduces the effect of input voltage and frequency disturbances on the protected load.

When the UPS transfers from normal operation to battery operation, the specified transfer time is 0ms. This avoids a transfer interruption caused by switching between the normal AC source and battery-powered inverter operation.

Key technical characteristics include:

  • Continuous inverter-based power conditioning.

  • Pure sine wave output.

  • Output voltage regulation of ±1%.

  • Battery-mode output frequency accuracy of ±0.01% at 50Hz or 60Hz.

  • Zero transfer time between mains and battery modes.

For manufacturing plants, this operating principle can help protect PLCs, industrial computers, machine controllers, and other electronic equipment against short-duration supply interruptions.

The actual performance under sudden load changes should be verified against the manufacturer’s dynamic-response test results.

Low Input Harmonic Distortion and Improved Power Quality

High-capacity UPS systems can affect the upstream electrical network through their input current characteristics. Harmonic current distortion can increase losses and interact with other equipment connected to the same supply.

The ET200K specifies an input current total harmonic distortion (THDi) of less than 3% at full load.

Its input power factor is greater than 0.95.

Electrical parameterET200K ratingPractical significance
Input power factorGreater than 0.95Supports efficient utilization of the upstream supply
Input current THDiLess than 3% at full loadLimits harmonic current distortion under the specified test condition
Input voltage range304–456VacAccommodates input voltage variation
Input frequency range40–70HzSupports a wide range of input frequency conditions
Input frequency selection50/60Hz, automaticAdapts to compatible nominal supply frequencies

These characteristics are relevant to industrial sites with generators, variable-frequency drives, automation equipment, and other nonlinear loads.

However, final generator sizing should consider rectifier behavior, battery charging demand, generator transient response, and the site’s complete load profile. Low THDi alone does not guarantee compatibility with every generator.

Industrial UPS Manufacturing ET200K 200kVA Assembly Process

 

IGBT-Based Rectifier for Improved Input Power Quality

The ET200K online UPS 200kVA uses an IGBT-based rectifier to convert incoming three-phase AC power into DC power for the DC bus. This rectifier topology supports controlled input current, a high input power factor of greater than 0.95, and input current total harmonic distortion (THDi) of less than 3% at full load.

  • THDi below 3% at full load helps reduce harmonic current injected into the upstream electrical network.
  • Greater than 0.95 supports efficient utilization of the AC supply.
  • IGBT switching enables active regulation of input current and DC-bus power, subject to the rectifier’s control design.
  • Suitable for applications where input power quality and stable DC-bus operation are important.

Regulated Output for Sensitive Industrial Loads

Industrial electronics may malfunction when voltage deviates beyond the permitted operating range. Repeated disturbances can also cause unnecessary shutdowns and production interruptions.

The ET200K provides an output voltage regulation specification of ±1% and low output voltage harmonic distortion.

Output characteristicET200K specification
Rated output voltage380/400/415Vac
Output voltage regulation±1%
THDu at 100% linear loadLess than 2%
THDu at 100% nonlinear loadLess than 5%
Output frequency in battery mode50/60Hz ±0.01%
Crest factor3:1
Output waveformPure sine wave

The low specified THDu helps supply sensitive electronic equipment with a cleaner voltage waveform. The 3:1 crest factor indicates the stated capability to accommodate loads with high peak-to-RMS current ratios, subject to the UPS’s rated current and overload limits.

For equipment with high starting current, such as motors and compressors, engineers must also evaluate starting current, acceleration time, load sequencing, and voltage-dip tolerance.

An online ups 200kva should therefore be selected based on both steady-state demand and transient load requirements.

Built-in Output Isolation Transformer

The ET200K 200kVA industrial online UPS integrates an output isolation transformer to provide galvanic isolation between the UPS inverter output and the connected load. This transformer-based design supports industrial power distribution requirements and offers greater flexibility in output grounding and neutral configuration, subject to the system design.

  • Galvanic isolation at the output: Electrically separates the inverter output circuit from the load circuit through the transformer.
  • Flexible grounding configuration: Supports grounding and neutral arrangements tailored to the installation requirements.
  • Industrial load compatibility: Suitable for industrial automation, manufacturing equipment, process control systems, and other critical loads requiring transformer-based power protection.
  • Robust power distribution: Provides an additional transformer interface between the UPS power conversion stage and downstream equipment.

Overload Capacity and Industrial Load Management

Industrial equipment does not always draw a constant amount of power. Motors start and stop. Compressors cycle. CNC machines change operating states. Transformer energization and capacitor charging can also create short-duration current peaks.

The ET200K specifies graduated overload handling, with transfer to bypass at defined load levels and durations.

Load relative to rated capacitySpecified overload behavior
Up to 105%Continuous operation
Above 105% to 110%Transfer to bypass within 60 minutes
Above 110% to 125%Transfer to bypass within 10 minutes
Above 125% to 150%Transfer to bypass within 1 minute
Above 150% to 200%Transfer to bypass within 200ms
Above 200%Inverter shutdown within 100ms and transfer to bypass output

These values describe the specified overload response, not a recommendation to operate the UPS continuously above its rated capacity.

A properly sized industrial UPS can accommodate temporary load variations within its documented limits. However, overload operation may transfer the load to bypass, where the load becomes dependent on the bypass supply’s availability and quality.

For demanding applications, confirm the bypass source capacity, upstream protection coordination, and acceptable load interruption risk before finalizing the design.

Energy Efficiency and Operating Cost

Energy efficiency affects the lifetime cost of an industrial UPS. Even a small efficiency difference can result in substantial energy losses when the system operates continuously at high load.

The ET200K specifies:

  • AC-to-AC efficiency above 93% in normal operating mode at full load.

  • ECO mode efficiency above 98%.

Normal Mode vs. ECO Mode

ComparisonOnline double-conversion modeECO mode
Specified efficiencyGreater than 93% at full loadGreater than 98%
Main operating principleContinuous inverter-based power conditioningLoad supplied through the bypass path under acceptable conditions
Output conditioningContinuous double conversionDepends on bypass supply quality and operating limits
Typical priorityPower conditioning and load protectionEnergy savings where bypass operation is acceptable

ECO mode can reduce conversion losses. However, its suitability depends on the site’s power quality requirements and tolerance for changes in operating mode.

For sensitive industrial loads, the efficiency gain should be weighed against the required protection level. Confirm the actual ECO-mode voltage and frequency limits before enabling it.

Prostar ET200K 200kVA Industrial UPS – Assembly in Progress

 

Illustrative Energy-Loss Calculation

At a hypothetical constant output load of 160kW, using the stated minimum efficiency figures as illustrative calculation points:

  • At 93% efficiency, input power would be approximately 172.0kW, giving about 12.0kW of conversion losses.

  • At 98% efficiency, input power would be approximately 163.3kW, giving about 3.3kW of conversion losses.

The difference is approximately 8.7kW, or 76MWh over 8,760 operating hours.

These are illustrative estimates, not guaranteed operating results. The datasheet values are specified as greater than 93% and greater than 98%; actual efficiency depends on load, configuration, and operating conditions.

Battery Configuration and Backup-Time

The ET200K supports VRLA batteries as standard, with lithium-ion battery compatibility available as an option. Its default DC battery voltage is 384Vdc, with a specified range of 336–384Vdc.

Battery autonomy depends on the connected load, battery capacity, discharge characteristics, ambient temperature, battery age, and inverter efficiency.

Battery parameterET200K specification
Standard battery typeVRLA
Optional battery typeLithium-ion
Default battery voltage360Vdc
Specified battery voltage range336–384Vdc
Charging configurationAdjustable charging rate, battery capacity, and battery group settings
Battery autonomyDetermined by battery configuration and load

How to Estimate Required Battery Capacity

This calculation evaluates the VRLA lead-acid battery configuration required for the Prostar ET200K 200kVA/200kW industrial online UPS, assuming 100% load and 15 minutes of backup time.

1. Battery Sizing Parameters

ParameterValue
UPS rated capacity200kVA / 200kW
Load level100%
UPS efficiency assumption93%
Illustrative nominal DC battery voltage384VDC
Individual battery rated voltage12V
Batteries connected in series per string32
Required backup time15 minutes
Battery aging factor (EOL)1.25
Safety margin5%
Battery model12V, 250Ah VRLA
Preliminary capacity target750Ah
Capacity target including 5% safety margin787.5Ah, approximately 788Ah

The capacity figures above are preliminary design targets. They do not independently establish that the proposed battery bank can supply 200kW for 15 minutes.

2. Required Battery-Side Power

At a 200kW output load and an assumed UPS efficiency of 92%, the estimated DC input power is:

PDC=200,000 /0.92 =217,391.3W

At the nominal battery voltage of 384VDC, the estimated DC current is:

IDC=217,391.3 / 384 = 566.1A

These are preliminary estimates based on nominal battery voltage. Actual battery current will increase as the battery voltage falls during discharge. Final sizing must use the manufacturer’s constant-power discharge data at the specified end-of-discharge voltage.

3. Constant-Current Discharge Data for a 12V, 250Ah Battery

The following manufacturer data show the constant-current discharge capability at 25°C (77°F).

Time15min30min1hr3hr5hr10hr20hr
9.60V40524714865.946.926.513.9
10.20V37523314264.045.125.713.5
10.50V35622313662.144.125.413.3
10.80V33421012960.843.025.013.2
11.10V30018911656.340.023.512.5

For a 200kW UPS, battery sizing should prioritize the constant-power discharge table because the UPS must sustain the required power as battery voltage declines.

4. Constant-Power Discharge Data for a 12V, 250Ah Battery

The following manufacturer data specify constant-power discharge performance in watts per block at 25°C (77°F).

Time15min30min1hr3hr5hr10hr20hr
9.60V445527661672744537303161
10.20V430026801633736521297159
10.50V409425751577720511294157
10.80V386924461509711503291155
11.10V351022301369664474278150

5. Number of Batteries Connected in Series

For a 384VDC battery system using 12V batteries:

Nseries = 384 / 12 =32

Therefore, 32 batteries connected in series form one battery string. This calculation is correct.

However, one string does not necessarily provide sufficient power or backup time for a 200kW load. The required number of parallel strings must be determined from the battery discharge data.

6. Parallel Strings and Total Battery Capacity

For 12V, 250Ah batteries, the nominal capacity of each string is 250Ah. Connecting strings in parallel increases the total amp-hour capacity while retaining the same nominal DC voltage.

ParameterThree parallel stringsFour parallel strings
Batteries per string3232
Number of parallel strings34
Total number of batteries96128
Nominal DC voltage384V384V
Nominal total capacity750Ah1000Ah

A three-string configuration provides 750Ah nominal capacity. Applying a 5% safety margin to this capacity target gives:

750 * 1.05 = 787.5Ah

This is approximately 788Ah. However, the safety margin does not increase the installed capacity of a three-string bank; it is a design allowance used when determining the required battery capacity.

For lithium-ion configurations, verify battery management system (BMS) compatibility, communication protocols, charge/discharge limits, and protection coordination.

Parallel Operation and System Availability

The ET200K supports parallel operation of up to 8 units. This provides options for capacity expansion and system-level redundancy.

Parallel operation does not automatically guarantee N+1 redundancy. The number of units, total load, redundancy target, bypass arrangement, and failure scenarios must all be evaluated.

Configuration exampleTotal installed capacityCapacity after one unit is unavailable
2 × 200kVA400kVA200kVA
3 × 200kVA600kVA400kVA
4 × 200kVA800kVA600kVA

The examples assume equal capacity sharing and that the remaining units can continue operating within their ratings. They do not confirm a specific redundancy implementation or fault-isolation behavior.

For a 200kW critical load, two 200kW units could theoretically provide N+1 capacity because one unit can carry the full load. Actual suitability depends on load growth, transient requirements, redundancy controls, and the manufacturer’s approved parallel configuration.

Before deployment, confirm synchronization, load sharing, parallel communication, bypass coordination, and maintenance procedures.

Monitoring, Protection, and Communication

Industrial power protection requires visibility into system status and the ability to identify faults quickly.

The ET200K includes a 7-inch LCD touchscreen and audible and visual alarms prioritized by severity.

Built-In Protection Functions

The specified protection functions include:

  • Output short-circuit protection.

  • Output overload protection.

  • Overtemperature protection.

  • Low battery voltage protection.

  • Output overvoltage and undervoltage protection.

  • Fan failure protection.

The enclosure is rated IP30, and cooling is provided by fans. The specified operating temperature range is 0°C to 40°C.

The online ups 200kva also provides several communication interfaces for integration with monitoring and control systems.

Interface or featureAvailability
RS232Standard
RS485Standard
USBStandard
Dry contactsStandard
Emergency Power Off (EPO)Standard
SNMP/Web monitoring interface slotOptional interface
Battery temperature compensationOptional
LCD touchscreen7-inch

SNMP and web-based monitoring can help operators integrate UPS status into centralized monitoring environments, subject to the selected communication card and software.

For industrial facilities, confirm which parameters are exposed through each interface, including alarms, input/output measurements, battery status, and event logs.

Industrial Applications

The ET200K is intended for high-capacity three-phase power protection. Its suitability for each application depends on the load profile, power quality requirements, autonomy target, and installation environment.

CNC Machines and Precision Manufacturing

CNC controllers, industrial PCs, and machine automation systems can be sensitive to short-duration power interruptions. The ET200K provides regulated AC output and zero specified transfer time to battery operation.

Commercial and institutional facilities

Can protect selected critical circuits in office buildings, laboratories, control centers, and other facilities requiring three-phase backup power.

Compressor Systems and Motor-Driven Equipment

Compressor controls and associated process electronics can benefit from conditioned power. Motor starting must be assessed separately, including starting current, acceleration time, and bypass capacity.

Industrial Automation and Robotics

Supplies backup power to PLCs, industrial robots, motion controllers, and automated production lines.

Manufacturing Production Lines

Protects control systems, inspection equipment, and other critical loads where unexpected power loss can interrupt production.

Technical Specifications

industrial equipment buyers.

ItemET200K specification
ModelET200K
Rated capacity200kVA/200kW
TopologyOnline double conversion
Input voltage380/400/415Vac, default 380Vac
Input voltage range304–456Vac
Input frequency50/60Hz, automatic
Input frequency range40–70Hz
Input power factorGreater than 0.95
Input THDiLess than 3% at full load
Output voltage380/400/415Vac ±1%
Output power factor1.0
Output THDuLess than 2% linear; less than 5% nonlinear load
Transfer time0ms
Full-load AC efficiencyGreater than 93%
ECO mode efficiencyGreater than 98%
Battery voltage384Vdc nominal; 336–384Vdc range
Parallel operationUp to 8 units
Protection ratingIP30
CoolingFan cooling
Operating temperature0°C to 40°C
Dimensions (W × D × H)1210 × 800 × 2000mm
Weight1000kg
NoiseLess than 65dBA at 1m, front side

Installation note: The specified weight is 1,000kg. Confirm floor loading, access routes, lifting arrangements, cable entry, ventilation clearance, and battery placement before installation.

Frequently Asked Questions (FAQ)

What is the rated output power of the ET200K 200kVA three-phase online UPS?

The ET200K is rated at 200kVA/200kW, with an output power factor of 1.0. Its nominal output voltage is 380V, 400V, or 415V AC, three-phase.

Is a 200kVA industrial UPS suitable for CNC machines and compressor systems?

It can be suitable for their control electronics and compatible electrical loads. However, motor starting current, acceleration profiles, peak demand, and bypass capacity must be checked before selecting the UPS for direct motor loads.

Can the ET200K 200kVA UPS use lithium-ion batteries?

Yes. VRLA batteries are standard, and lithium-ion battery compatibility is available as an option. Battery voltage, BMS communication, charging limits, and protection settings must be verified for the selected battery system.

Can the ET200K industrial UPS operate in parallel for N+1 redundancy?

The ET200K supports parallel operation of up to eight units. N+1 redundancy depends on the number of installed units, total load, parallel control configuration, and bypass design. Parallel capability alone does not guarantee redundancy.

The Articles You may Like

 

ModelET200K
Capacity200KVA/200KW
TopologyDouble conversion online
Noise<65dBA  front side 1M
Dimension(WxDxH mm)1210x800x2000
Weight(Kgs)1000
INPUT
Input Rated Voltage3P + N + PE, 380Vac/400Vac/415Vac(Default 380Vac)
Input Voltage Range304Vac – 456Vac
Input Rated Frequency50Hz/60Hz (Auto)
Input Frequency Range40Hz – 70Hz
Input Power Factor>0.95
Input Current Limit1.25 times Rated INPUT Current (Settable 0.1 – 1.25)
THDI< 3% full load
BYPASS INPUT
Bypass Input Voltage Range304Vac – 456Vac
Bypass Input Voltage RegulationUpper Limit: default 20% (Settable 10%/15%/20%/25%)
Lower Limit: default 20% (Settable 10%/20%/30%/40%/50%/60%)
OUTPUT
Output Rated Voltage3P + N + PE, 380Vac/400Vac/415Vac ± 1%
Output Voltage Regulation0V(Settable ±1V- ±5V)
Output FrequencyMains Mode: tracking BYPASS Input in synchronized state
Battery Mode: 50Hz/60Hz±0.01%
Output Power Factor1
Total Harmonic Distortion (THDU)< 2% at 100% linear load; < 5% at 100% non-linear load
Overload CapacityLoad ≤ 105%, long time work;
105% < load ≤ 110%, transfer to bypass in 60 mins
110% < load ≤ 125%, transfer to bypass in 10 mins
125% < load ≤ 150%, transfer to bypass in 1 min
150% < load ≤ 200%, transfer to bypass in 200 ms
200% < load, inverter off (UPS shutdown) in 100 ms and transfer to bypass output
Crest Factor3:1
Wave FormPure sine wave
Transfer Time0ms
ECO MODE
Bypass Output Voltage RegulationUpper Limit: default 5% (Settable 5%/10%/15%)
Lower Limit: default 5% (Settable 5%/10%/15%)
Bypass Output Frequency RegulationDefault ±2Hz (Settable ±1Hz/±2Hz/±3Hz)
EFFICIENCY
Efficiency at full load (AC-AC)>93%
Efficiency at ECO Mode>98%
BATTERY
Battery TypeSupport VRLA Battery, (Lithium-ion Battery Option)
Battery VoltageDefault 360Vdc (336VDC-384VDC)
Battery Charging CurrentCharging Rate * Battery Capacity * Group of Battery (Settable for charging rate, battery capacity and group of battery)
SYSTEM
ProtectionOutput short circuit protection, output overload protection, over-temperature protection, low battery voltage protection, output overvoltage / undervoltage protection, fan failure protection
IP ProtectionIP30
Number of Parallel< 8 Units
Cooling MethodFans
Display7-inch LCD Touch Screen
Audible AlarmAudible and visible alarms prioritized by severity
ENVIRONMENT
Operating Temperature0℃ to 40℃ (32F-104F)
Humidity0~95% (non-condensing)
Altitude< 1000m (Capacity de-rates by 1% for every 100m over 1000m)
Storage Temperature-20℃ to 70℃
COMMUNICATION
Communication InterfaceDefault: RS232/RS485/USB/Dry Contact/EPO (Option: Battery Temperature Compensation)
Communication SlotSNMP/Web interface
Prostar 150x40
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.