3 Phase UPS | 200KVA/200KW | 380V/400V/415V | Battery Voltage: 360Vdc
Prostar ET200K is three-phase industrial online UPS 200kVA designed to protect critical equipment against power interruptions and voltage disturbances. It features double-conversion technology, a 1.0 output power factor, less than 3% input current THDi at full load, zero transfer time, and support for up to eight parallel units. VRLA batteries are standard; lithium-ion compatibility is optional.
The system uses online double-conversion technology to regulate output power independently of normal input voltage fluctuations. It delivers a pure sine wave output, supports three-phase, four-wire-plus-protective-earth connections, and provides a nominal output voltage of 380V, 400V, or 415V AC.
For applications requiring higher system capacity or parallel redundancy, the ET200K online UPS 200kVA supports parallel operation of up to 8 units.
Selecting an industrial UPS requires more than matching the nominal kVA rating. Engineers must evaluate active power capacity, voltage stability, harmonic distortion, overload performance, battery autonomy, and maintenance requirements.
The ET200K combines a 200kVA rating with 200kW of active power. This makes the online ups 200kva suitable for facilities with high power demand and equipment sensitive to voltage disturbances.

Many industrial loads require substantial active power to operate motors, automation systems, control equipment, and production machinery. A UPS with a lower output power factor may reach its kW limit before reaching its kVA limit.
The ET200K has a rated output power factor of 1.0.
| Parameter | ET200K specification | Engineering benefit |
|---|---|---|
| Rated apparent power | 200kVA | Defines the UPS capacity in kVA |
| Rated active power | 200kW | Supports up to 200kW of rated active load |
| Output power factor | 1.0 | Makes rated kVA equal to rated kW |
| Output voltage | 380/400/415Vac | Supports common three-phase industrial distribution voltages |
| Output waveform | Pure sine wave | Suitable for sensitive electronic loads |
It means the ET200K can deliver up to 200kW of active power at its rated conditions. Actual system sizing must also account for load current, power factor, harmonic content, transient demand, and the manufacturer’s operating limits.
For example, a facility with a 160kW steady-state load would use 80% of the UPS’s rated active power. This leaves 40kW of nominal active-power headroom, although transient loads and future expansion must be assessed separately.
The ET200K uses online double-conversion technology. Incoming AC power is converted to DC and then reconstructed as regulated AC power through the inverter.
This process reduces the effect of input voltage and frequency disturbances on the protected load.
When the UPS transfers from normal operation to battery operation, the specified transfer time is 0ms. This avoids a transfer interruption caused by switching between the normal AC source and battery-powered inverter operation.
Key technical characteristics include:
Continuous inverter-based power conditioning.
Pure sine wave output.
Output voltage regulation of ±1%.
Battery-mode output frequency accuracy of ±0.01% at 50Hz or 60Hz.
Zero transfer time between mains and battery modes.
For manufacturing plants, this operating principle can help protect PLCs, industrial computers, machine controllers, and other electronic equipment against short-duration supply interruptions.
The actual performance under sudden load changes should be verified against the manufacturer’s dynamic-response test results.
High-capacity UPS systems can affect the upstream electrical network through their input current characteristics. Harmonic current distortion can increase losses and interact with other equipment connected to the same supply.
The ET200K specifies an input current total harmonic distortion (THDi) of less than 3% at full load.
Its input power factor is greater than 0.95.
| Electrical parameter | ET200K rating | Practical significance |
|---|---|---|
| Input power factor | Greater than 0.95 | Supports efficient utilization of the upstream supply |
| Input current THDi | Less than 3% at full load | Limits harmonic current distortion under the specified test condition |
| Input voltage range | 304–456Vac | Accommodates input voltage variation |
| Input frequency range | 40–70Hz | Supports a wide range of input frequency conditions |
| Input frequency selection | 50/60Hz, automatic | Adapts to compatible nominal supply frequencies |
These characteristics are relevant to industrial sites with generators, variable-frequency drives, automation equipment, and other nonlinear loads.
However, final generator sizing should consider rectifier behavior, battery charging demand, generator transient response, and the site’s complete load profile. Low THDi alone does not guarantee compatibility with every generator.

The ET200K online UPS 200kVA uses an IGBT-based rectifier to convert incoming three-phase AC power into DC power for the DC bus. This rectifier topology supports controlled input current, a high input power factor of greater than 0.95, and input current total harmonic distortion (THDi) of less than 3% at full load.
Industrial electronics may malfunction when voltage deviates beyond the permitted operating range. Repeated disturbances can also cause unnecessary shutdowns and production interruptions.
The ET200K provides an output voltage regulation specification of ±1% and low output voltage harmonic distortion.
| Output characteristic | ET200K specification |
|---|---|
| Rated output voltage | 380/400/415Vac |
| Output voltage regulation | ±1% |
| THDu at 100% linear load | Less than 2% |
| THDu at 100% nonlinear load | Less than 5% |
| Output frequency in battery mode | 50/60Hz ±0.01% |
| Crest factor | 3:1 |
| Output waveform | Pure sine wave |
The low specified THDu helps supply sensitive electronic equipment with a cleaner voltage waveform. The 3:1 crest factor indicates the stated capability to accommodate loads with high peak-to-RMS current ratios, subject to the UPS’s rated current and overload limits.
For equipment with high starting current, such as motors and compressors, engineers must also evaluate starting current, acceleration time, load sequencing, and voltage-dip tolerance.
An online ups 200kva should therefore be selected based on both steady-state demand and transient load requirements.
The ET200K 200kVA industrial online UPS integrates an output isolation transformer to provide galvanic isolation between the UPS inverter output and the connected load. This transformer-based design supports industrial power distribution requirements and offers greater flexibility in output grounding and neutral configuration, subject to the system design.
Industrial equipment does not always draw a constant amount of power. Motors start and stop. Compressors cycle. CNC machines change operating states. Transformer energization and capacitor charging can also create short-duration current peaks.
The ET200K specifies graduated overload handling, with transfer to bypass at defined load levels and durations.
| Load relative to rated capacity | Specified overload behavior |
|---|---|
| Up to 105% | Continuous operation |
| Above 105% to 110% | Transfer to bypass within 60 minutes |
| Above 110% to 125% | Transfer to bypass within 10 minutes |
| Above 125% to 150% | Transfer to bypass within 1 minute |
| Above 150% to 200% | Transfer to bypass within 200ms |
| Above 200% | Inverter shutdown within 100ms and transfer to bypass output |
These values describe the specified overload response, not a recommendation to operate the UPS continuously above its rated capacity.
A properly sized industrial UPS can accommodate temporary load variations within its documented limits. However, overload operation may transfer the load to bypass, where the load becomes dependent on the bypass supply’s availability and quality.
For demanding applications, confirm the bypass source capacity, upstream protection coordination, and acceptable load interruption risk before finalizing the design.
Energy efficiency affects the lifetime cost of an industrial UPS. Even a small efficiency difference can result in substantial energy losses when the system operates continuously at high load.
The ET200K specifies:
AC-to-AC efficiency above 93% in normal operating mode at full load.
ECO mode efficiency above 98%.
| Comparison | Online double-conversion mode | ECO mode |
|---|---|---|
| Specified efficiency | Greater than 93% at full load | Greater than 98% |
| Main operating principle | Continuous inverter-based power conditioning | Load supplied through the bypass path under acceptable conditions |
| Output conditioning | Continuous double conversion | Depends on bypass supply quality and operating limits |
| Typical priority | Power conditioning and load protection | Energy savings where bypass operation is acceptable |
ECO mode can reduce conversion losses. However, its suitability depends on the site’s power quality requirements and tolerance for changes in operating mode.
For sensitive industrial loads, the efficiency gain should be weighed against the required protection level. Confirm the actual ECO-mode voltage and frequency limits before enabling it.

At a hypothetical constant output load of 160kW, using the stated minimum efficiency figures as illustrative calculation points:
At 93% efficiency, input power would be approximately 172.0kW, giving about 12.0kW of conversion losses.
At 98% efficiency, input power would be approximately 163.3kW, giving about 3.3kW of conversion losses.
The difference is approximately 8.7kW, or 76MWh over 8,760 operating hours.
These are illustrative estimates, not guaranteed operating results. The datasheet values are specified as greater than 93% and greater than 98%; actual efficiency depends on load, configuration, and operating conditions.
The ET200K supports VRLA batteries as standard, with lithium-ion battery compatibility available as an option. Its default DC battery voltage is 384Vdc, with a specified range of 336–384Vdc.
Battery autonomy depends on the connected load, battery capacity, discharge characteristics, ambient temperature, battery age, and inverter efficiency.
| Battery parameter | ET200K specification |
|---|---|
| Standard battery type | VRLA |
| Optional battery type | Lithium-ion |
| Default battery voltage | 360Vdc |
| Specified battery voltage range | 336–384Vdc |
| Charging configuration | Adjustable charging rate, battery capacity, and battery group settings |
| Battery autonomy | Determined by battery configuration and load |
This calculation evaluates the VRLA lead-acid battery configuration required for the Prostar ET200K 200kVA/200kW industrial online UPS, assuming 100% load and 15 minutes of backup time.
| Parameter | Value |
|---|---|
| UPS rated capacity | 200kVA / 200kW |
| Load level | 100% |
| UPS efficiency assumption | 93% |
| Illustrative nominal DC battery voltage | 384VDC |
| Individual battery rated voltage | 12V |
| Batteries connected in series per string | 32 |
| Required backup time | 15 minutes |
| Battery aging factor (EOL) | 1.25 |
| Safety margin | 5% |
| Battery model | 12V, 250Ah VRLA |
| Preliminary capacity target | 750Ah |
| Capacity target including 5% safety margin | 787.5Ah, approximately 788Ah |
The capacity figures above are preliminary design targets. They do not independently establish that the proposed battery bank can supply 200kW for 15 minutes.
At a 200kW output load and an assumed UPS efficiency of 92%, the estimated DC input power is:
At the nominal battery voltage of 384VDC, the estimated DC current is:
These are preliminary estimates based on nominal battery voltage. Actual battery current will increase as the battery voltage falls during discharge. Final sizing must use the manufacturer’s constant-power discharge data at the specified end-of-discharge voltage.
The following manufacturer data show the constant-current discharge capability at 25°C (77°F).
| Time | 15min | 30min | 1hr | 3hr | 5hr | 10hr | 20hr |
| 9.60V | 405 | 247 | 148 | 65.9 | 46.9 | 26.5 | 13.9 |
| 10.20V | 375 | 233 | 142 | 64.0 | 45.1 | 25.7 | 13.5 |
| 10.50V | 356 | 223 | 136 | 62.1 | 44.1 | 25.4 | 13.3 |
| 10.80V | 334 | 210 | 129 | 60.8 | 43.0 | 25.0 | 13.2 |
| 11.10V | 300 | 189 | 116 | 56.3 | 40.0 | 23.5 | 12.5 |
For a 200kW UPS, battery sizing should prioritize the constant-power discharge table because the UPS must sustain the required power as battery voltage declines.
The following manufacturer data specify constant-power discharge performance in watts per block at 25°C (77°F).
| Time | 15min | 30min | 1hr | 3hr | 5hr | 10hr | 20hr |
| 9.60V | 4455 | 2766 | 1672 | 744 | 537 | 303 | 161 |
| 10.20V | 4300 | 2680 | 1633 | 736 | 521 | 297 | 159 |
| 10.50V | 4094 | 2575 | 1577 | 720 | 511 | 294 | 157 |
| 10.80V | 3869 | 2446 | 1509 | 711 | 503 | 291 | 155 |
| 11.10V | 3510 | 2230 | 1369 | 664 | 474 | 278 | 150 |
For a 384VDC battery system using 12V batteries:
Therefore, 32 batteries connected in series form one battery string. This calculation is correct.
However, one string does not necessarily provide sufficient power or backup time for a 200kW load. The required number of parallel strings must be determined from the battery discharge data.
For 12V, 250Ah batteries, the nominal capacity of each string is 250Ah. Connecting strings in parallel increases the total amp-hour capacity while retaining the same nominal DC voltage.
| Parameter | Three parallel strings | Four parallel strings |
|---|---|---|
| Batteries per string | 32 | 32 |
| Number of parallel strings | 3 | 4 |
| Total number of batteries | 96 | 128 |
| Nominal DC voltage | 384V | 384V |
| Nominal total capacity | 750Ah | 1000Ah |
A three-string configuration provides 750Ah nominal capacity. Applying a 5% safety margin to this capacity target gives:
750 * 1.05 = 787.5Ah
This is approximately 788Ah. However, the safety margin does not increase the installed capacity of a three-string bank; it is a design allowance used when determining the required battery capacity.
For lithium-ion configurations, verify battery management system (BMS) compatibility, communication protocols, charge/discharge limits, and protection coordination.
The ET200K supports parallel operation of up to 8 units. This provides options for capacity expansion and system-level redundancy.
Parallel operation does not automatically guarantee N+1 redundancy. The number of units, total load, redundancy target, bypass arrangement, and failure scenarios must all be evaluated.
| Configuration example | Total installed capacity | Capacity after one unit is unavailable |
|---|---|---|
| 2 × 200kVA | 400kVA | 200kVA |
| 3 × 200kVA | 600kVA | 400kVA |
| 4 × 200kVA | 800kVA | 600kVA |
The examples assume equal capacity sharing and that the remaining units can continue operating within their ratings. They do not confirm a specific redundancy implementation or fault-isolation behavior.
For a 200kW critical load, two 200kW units could theoretically provide N+1 capacity because one unit can carry the full load. Actual suitability depends on load growth, transient requirements, redundancy controls, and the manufacturer’s approved parallel configuration.
Before deployment, confirm synchronization, load sharing, parallel communication, bypass coordination, and maintenance procedures.
Industrial power protection requires visibility into system status and the ability to identify faults quickly.
The ET200K includes a 7-inch LCD touchscreen and audible and visual alarms prioritized by severity.
The specified protection functions include:
Output short-circuit protection.
Output overload protection.
Overtemperature protection.
Low battery voltage protection.
Output overvoltage and undervoltage protection.
Fan failure protection.
The enclosure is rated IP30, and cooling is provided by fans. The specified operating temperature range is 0°C to 40°C.
The online ups 200kva also provides several communication interfaces for integration with monitoring and control systems.
| Interface or feature | Availability |
|---|---|
| RS232 | Standard |
| RS485 | Standard |
| USB | Standard |
| Dry contacts | Standard |
| Emergency Power Off (EPO) | Standard |
| SNMP/Web monitoring interface slot | Optional interface |
| Battery temperature compensation | Optional |
| LCD touchscreen | 7-inch |
SNMP and web-based monitoring can help operators integrate UPS status into centralized monitoring environments, subject to the selected communication card and software.
For industrial facilities, confirm which parameters are exposed through each interface, including alarms, input/output measurements, battery status, and event logs.
The ET200K is intended for high-capacity three-phase power protection. Its suitability for each application depends on the load profile, power quality requirements, autonomy target, and installation environment.
CNC controllers, industrial PCs, and machine automation systems can be sensitive to short-duration power interruptions. The ET200K provides regulated AC output and zero specified transfer time to battery operation.
Can protect selected critical circuits in office buildings, laboratories, control centers, and other facilities requiring three-phase backup power.
Compressor controls and associated process electronics can benefit from conditioned power. Motor starting must be assessed separately, including starting current, acceleration time, and bypass capacity.
Supplies backup power to PLCs, industrial robots, motion controllers, and automated production lines.
Protects control systems, inspection equipment, and other critical loads where unexpected power loss can interrupt production.
industrial equipment buyers.
| Item | ET200K specification |
|---|---|
| Model | ET200K |
| Rated capacity | 200kVA/200kW |
| Topology | Online double conversion |
| Input voltage | 380/400/415Vac, default 380Vac |
| Input voltage range | 304–456Vac |
| Input frequency | 50/60Hz, automatic |
| Input frequency range | 40–70Hz |
| Input power factor | Greater than 0.95 |
| Input THDi | Less than 3% at full load |
| Output voltage | 380/400/415Vac ±1% |
| Output power factor | 1.0 |
| Output THDu | Less than 2% linear; less than 5% nonlinear load |
| Transfer time | 0ms |
| Full-load AC efficiency | Greater than 93% |
| ECO mode efficiency | Greater than 98% |
| Battery voltage | 384Vdc nominal; 336–384Vdc range |
| Parallel operation | Up to 8 units |
| Protection rating | IP30 |
| Cooling | Fan cooling |
| Operating temperature | 0°C to 40°C |
| Dimensions (W × D × H) | 1210 × 800 × 2000mm |
| Weight | 1000kg |
| Noise | Less than 65dBA at 1m, front side |
Installation note: The specified weight is 1,000kg. Confirm floor loading, access routes, lifting arrangements, cable entry, ventilation clearance, and battery placement before installation.
| Model | ET200K |
| Capacity | 200KVA/200KW |
| Topology | Double conversion online |
| Noise | <65dBA front side 1M |
| Dimension(WxDxH mm) | 1210x800x2000 |
| Weight(Kgs) | 1000 |
| INPUT | |
| Input Rated Voltage | 3P + N + PE, 380Vac/400Vac/415Vac(Default 380Vac) |
| Input Voltage Range | 304Vac – 456Vac |
| Input Rated Frequency | 50Hz/60Hz (Auto) |
| Input Frequency Range | 40Hz – 70Hz |
| Input Power Factor | >0.95 |
| Input Current Limit | 1.25 times Rated INPUT Current (Settable 0.1 – 1.25) |
| THDI | < 3% full load |
| BYPASS INPUT | |
| Bypass Input Voltage Range | 304Vac – 456Vac |
| Bypass Input Voltage Regulation | Upper Limit: default 20% (Settable 10%/15%/20%/25%) Lower Limit: default 20% (Settable 10%/20%/30%/40%/50%/60%) |
| OUTPUT | |
| Output Rated Voltage | 3P + N + PE, 380Vac/400Vac/415Vac ± 1% |
| Output Voltage Regulation | 0V(Settable ±1V- ±5V) |
| Output Frequency | Mains Mode: tracking BYPASS Input in synchronized state Battery Mode: 50Hz/60Hz±0.01% |
| Output Power Factor | 1 |
| Total Harmonic Distortion (THDU) | < 2% at 100% linear load; < 5% at 100% non-linear load |
| Overload Capacity | Load ≤ 105%, long time work; 105% < load ≤ 110%, transfer to bypass in 60 mins 110% < load ≤ 125%, transfer to bypass in 10 mins 125% < load ≤ 150%, transfer to bypass in 1 min 150% < load ≤ 200%, transfer to bypass in 200 ms 200% < load, inverter off (UPS shutdown) in 100 ms and transfer to bypass output |
| Crest Factor | 3:1 |
| Wave Form | Pure sine wave |
| Transfer Time | 0ms |
| ECO MODE | |
| Bypass Output Voltage Regulation | Upper Limit: default 5% (Settable 5%/10%/15%) Lower Limit: default 5% (Settable 5%/10%/15%) |
| Bypass Output Frequency Regulation | Default ±2Hz (Settable ±1Hz/±2Hz/±3Hz) |
| EFFICIENCY | |
| Efficiency at full load (AC-AC) | >93% |
| Efficiency at ECO Mode | >98% |
| BATTERY | |
| Battery Type | Support VRLA Battery, (Lithium-ion Battery Option) |
| Battery Voltage | Default 360Vdc (336VDC-384VDC) |
| Battery Charging Current | Charging Rate * Battery Capacity * Group of Battery (Settable for charging rate, battery capacity and group of battery) |
| SYSTEM | |
| Protection | Output short circuit protection, output overload protection, over-temperature protection, low battery voltage protection, output overvoltage / undervoltage protection, fan failure protection |
| IP Protection | IP30 |
| Number of Parallel | < 8 Units |
| Cooling Method | Fans |
| Display | 7-inch LCD Touch Screen |
| Audible Alarm | Audible and visible alarms prioritized by severity |
| ENVIRONMENT | |
| Operating Temperature | 0℃ to 40℃ (32F-104F) |
| Humidity | 0~95% (non-condensing) |
| Altitude | < 1000m (Capacity de-rates by 1% for every 100m over 1000m) |
| Storage Temperature | -20℃ to 70℃ |
| COMMUNICATION | |
| Communication Interface | Default: RS232/RS485/USB/Dry Contact/EPO (Option: Battery Temperature Compensation) |
| Communication Slot | SNMP/Web interface |