3 Phase Online UPS | 10kVA / 10kW | 3 Phase | Built-in 20x12V 9AH Battery
Prostar PET3310B 3 phase double conversion online ups 10kva with battery for mission-critical applications. The online ups 10kva with battery provides true online double-conversion technology. It features full DSP digital control. This ensures zero transfer time and the highest level of power quality.
double conversion online ups 10kva with battery supports wide input voltage (167-250Vac) and frequency ranges (40-70Hz). This makes it ideal for harsh environments or generator compatibility. Advanced DSP and IGBT ensure low THDi (<3%) and high efficiency. Efficiency reaches up to 93% in double conversion mode or over 98% in ECO mode. Multi-communication options like RS232, USB, SNMP, and dry contacts enable remote monitoring.

Transformerless High-Frequency Design
Compact size, lighter weight, higher efficiency (up to 95.5% in online mode, even higher in ECO mode).
Unity Output Power Factor (PF=1.0)
10kVA = 10kW full active power output, maximizing usable capacity without derating.
Full-phase Active Input Power Factor Correction (PFC)
Input PF ≥ 0.99, greatly reducing harmonic pollution and improving grid compatibility.
Parallel Operation Capability
Supports multiple units in parallel for capacity expansion or N+1 redundancy, enhancing system availability.
Smart Monitoring & Communication
Standard RS232 / USB / dry contacts; optional SNMP card for remote monitoring via network; supports EPO (Emergency Power Off)
4.3-inch Touchscreen LCD Display
Intuitive, full-color graphical interface shows real-time parameters like input/output voltage and frequency. It also displays load percentage, battery status, runtime, faults, and more. The interface offers multilingual support for easy local monitoring and configuration.
The online double-conversion UPS acts as the core of the system. It continuously converts incoming AC power to DC. Then it converts the DC back to clean, regulated AC power. This design fully isolates the load from input power disturbances such as voltage fluctuations, frequency variations, and electrical noise.
An external battery bank or battery cabinet is connected to the UPS to provide uninterrupted backup power during mains failure. The UPS automatically switches to battery mode without interruption, ensuring continuous operation of connected equipment.
The conditioned and regulated output power from the UPS is delivered to various critical loads. This includes servers, data centers, security systems, networking equipment, and industrial devices. This ensures maximum protection and reliability.
| 1. SNMP intelligent slot | 2. Cold start function | 3. RS485 communication port |
| 4. RS232 communication port | 5. USB communication port | 6. Emergency power off function connector |
| 7. Share current port(only for parallel model) | 8. Parallel port (only for parallel model) | 9. Line input circuit breaker/switch |
| 10. Manual bypass switch (10kVA – 40kVA optional configuration) | 11. Output switch | 12. Maintenance bypass switch |
| 13. Line connection terminal | 14. Bypass input terminal (10kVA-40kVA optional configuration) | 15. Battery switch |


Dual Input in Parallel Operation

10kVA UPS with 20 units 12V 9AH VLRA battery




Power Range: 10kVA/10kW
Output Power Factor: 1.0
Input Phase: Three-phase (3P + N + PE)
Nominal Voltage: 380 / 400 / 415 Vac
Voltage Range: 110Vac – 300Vac (P-N)
Frequency: 50 / 60 Hz (auto-sensing)
Power Factor: ≥ 0.99
Input THDi: ≤ 3%
Output Phase: Three-phase (3P + N + PE)
Output Voltage: 380 / 400 / 415 Vac
Voltage Regulation: ±1%
Frequency Accuracy:
Utility mode: synchronized to input
Battery mode: ±0.1Hz
Waveform: Pure sine wave
Total Harmonic Distortion (THDv):
Linear load: ≤ 2%
Non-linear load: ≤ 5%
Battery Type: VRLA battery
Battery Configuration: Built-in 20x12V 9AH VRLA Battery
Charging Method: Intelligent multi-stage charging
Parallel Capability: Up to 4 units
Parallel Mode: Capacity expansion or N+1 redundancy
Display: LCD + LED indicators
Standard Interface: RS232 / RS485 / USB
Optional Interface: SNMP, WiFi, GPRS, Dry Contact
Monitoring: Local and remote real-time monitoring
Design: Transformerless, high-frequency
Installation: Tower / Cabinet type
Cooling: Intelligent forced air cooling
Protection Level: IP20
Carefully unpack the UPS on a stable surface. Check for shipping damage (dents, scratches, loose parts). Verify all accessories: user manual, parallel cables (if applicable), communication cables, mounting hardware, and terminal covers. Report any issues to the supplier immediately. Do not install a damaged unit.
| Model | PET3310B |
| Capacity | 10KVA/10KW |
| Topology | Double conversion online |
| Noise | Less than 55dBA front side 1M |
| Dimension(WxDxH mm) | 250x828x863 |
| Weight(Kg) | 93 |
| INPUT | |
| Low Line Loss Voltage | 110VAC(L-N) ± 3% at 50% load, 176VAC(L-N) ± 3% at 100% load |
| Low Line Comeback Voltage | Low line loss voltage + 10V |
| High Line Loss Voltage | 300VAC(L-N) ± 3% at 50% load, 276VAC(L-N) ± 3% at 100% load |
| High Line Comeback Voltage | High line loss voltage -10V |
| Input Frequency Range | 50Hz: 46-54Hz, 60Hz: 56-64Hz |
| Input Power Factor | ≥0.99 at 100% load |
| OUTPUT | |
| Output Rated Voltage | 3P + N + PE, 360Vac/380Vac/400Vac/415Vac ± 1% |
| Output Frequency | AC mode: 50Hz: 46-54Hz, 60Hz: 56-64Hz; Battery mode: 50Hz/60Hz ± 0.1Hz |
| Output Power Factor | 1 |
| Total Harmonic Distortion | ≤ 2% at 100% linear load; ≤ 5% at 100% non-linear load |
| Overload Capacity | AC mode: 100%-110%: 60mins; 110%-125%: 10mins; 125%-150%: 1min; >150%: immediately Battery mode: 100%-110%: 60mins; 110%-125%: 10mins; 125%-150%: 1min; >150%: immediately |
| Crest Factor | 3:1 |
| Wave Form | Pure sine wave |
| Transfer Time | Line –> Battery: 0ms; Inverter –>Bypass: 0ms(When phase lock fails, <4ms interruption occus from inverter to bypass); Inverter –> ECO: <10ms |
| EFFICIENCY | |
| Efficiency at full load (AC-AC) | >95.5% |
| Efficiency at battery mode | >94.5% |
| BATTERY | |
| Battery Type | Lead Acid Battery |
| Battery Number | 20 x 12V 9AH |
| Battery Voltage | +/- 120VDC |
| Battery Charging Current | 2A default, 1A – 12A ± 10% adjustable |
| Battery Charging Voltage | +/- 136.5VDC ± 1% |
| SYSTEM | |
| IP Protection | IP20 |
| Number of Parallel | < 6 Units |
| Cooling Method | Fans |
| Display | 7-inch LCD Touch Screen |
| Audible Alarm | Audible and visible alarms prioritized by severity |
| ENVIRONMENT | |
| Operating Temperature | 0℃ to 40℃ (battery life will down when >25℃) |
| Humidity | 0~95% (non-condensing) |
| Altitude | < 1000m (Capacity de-rates by 1% for every 100m over 1000m) |
| COMMUNICATION | |
| Communication Interface | RS232/RS458/USB |
| Communication Slot | Optional SNMP |