Prostar 20kVA to 300kVA Modular UPS system

SKU: MPS90K-30U - MPS300K-42U Category:

Mars Series Modular UPS uses high efficient online double conversion technology, and the efficiency can reach 94.5%. And it’s seamless integrated with the latest data room designs, which is a high-reliability redundant scalable modular UPS systems.

Mars Series Modular UPS system with extremely flexible architecture, and it’s power modules using online hot-swappable design, which can easily be removed, installed and maintained when the system is running, but without affecting system operation and output, which made the investment plan comes true according to the requirement. Which could both to meet the user extended equipment needs at later period, but also reduce the initial purchase cost.

Mars Series Modular UPS provides 20KW and 30KW power modules and two kinds of cabinets system, the user can be flexibly configured according to the load demand. The single cabinet can achieve maximum capacity up to 300KW, and provide 2 kinds ups system of 90KW and 120KW, which could be with built-in battery modules, for users choose easily.

Cabinet ModelMPS90K-30UMPS120K-42UMPS120K-30UMPS180K-30UMPS210K-42UMPS300K-42U
Maximum Capacity90KW120KW80KW/120KW120KW/180KW210KW300KVA
Phase3-phase in / 3-phase out
Battery Voltage240V Default, 192V/240V Selectable
Battery TypeBuilt-in Battery ModuleExternal Battery Pack
Power Module Capacity30KW20KW/30KW30KW30KW
Max. Power Module NO.34467+110
Max. Battery Module NO.35––––
Size, D X W X H (mm)1100X600X14751100 X600X20101100 X600X14751100 X600X2010
Cabinet Net Weight (Kgs)675932333/335435/438515/549618
Input
Input Voltage3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Range305~477VAC at 100% Load; 208~304VAC at <70% Load
Nominal Frequency50/60Hz(Auto Sensing)
Frequency Range40Hz~70Hz
Power Factor>0.99 @ 100% Load, >0.98 @ 50% Load
Harmonic Distortion (THDi)< 3% @ 100% Load
Output
Nominal Voltage3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation(Steady state)≦±1%Typical(Balanced Load);≦±2% Typical (Unbalanced Load)
Voltage Regulation(Transient)≦±5% Typical
Nominal Frequency50/60Hz
Frequency Range(Synchronized)46Hz~54Hz or 56Hz~64Hz
Overload Capability1 hour for 110%,10 min for 120%,1 min for 150%,200ms for >150%
Harmonic Distortion≦1.5% THD(Linear Load);≦4% THD( Non-linear Load )
EfficiencyUp to 94.5%
Battery/Charger
Nominal Voltage+/- 216V (12V x 36Pcs)
Maximum Voltage+/- 240V (12V x 40Pcs)
Minimum Voltage+/- 192V (12V x 32Pcs)
Float Charging Voltage2.25V/Cell
Boost Charging Voltage2.35V/Cell
Temperature CompensationYes
Maximum Charging Current8A for each power module (User adjustable)
Standards
SafetyIEC/EN 60950-1; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3
Environment
Operation Temperature0~40°C
Relative Humidity0~95% Non-condensing
Altitude<1000m for Nominal power
IP ClassIP20
Management
Smart RS-232 or USBWindows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC
Optional SNMPPower management from SNMP manager and web browser

Leave a Reply

Prostar 150x40
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.